DALTON UPS U31 PLUS SERIES

Dalton Ups U31 Plus Series Online Transformer based UPS
Three – Single phase Input / Single Phase output 10kVA – 40kVA
Latest double conversion technology.
The Dalton UPS U31 Series can be installed with internal batteries as standard.
This removes the need for external battery cabinets on standard run times, enabling you to maximize valuable floor space.
Additional flexibility is achieved for the U31 Series through its sophisticated design.
The selectable input between single phase and three phases allow users to retain electrical infrastructure and save costs where applicable
– Online double conversion topology
– High efficiency up to 96%
– Intelligent monitoring software
– EPO connection
– Wide input voltage window
Specifications
Model | U31PLUS10000 10KVA |
U31PLUS15000 15KVA |
U31PLUS20000 20KVA |
U31PLUS30000 30KVA |
U31PLUS40000 40KVA |
|
Rating Power |
10KVA / 8000W
|
15KVA /12000W | 20KVA /16000W | 30KVA / 24000W | 40KVA / 32000W | |
Input | Input system | Three Phase - Single Phase | ||||
Voltage range | 230-495VAC / 176-276VAC (100% load), 120-276VAC (50% load) | |||||
Power factor | ≥0.99 | |||||
Frequency | 50/60Hz | |||||
Output | Output system | Single Phase | ||||
Rated voltage | 200/208/220/230VAC | |||||
Power factor | 0.8 | |||||
Voltage precision | ±1% | |||||
Voltage distortion | < 3% THDV on non-linear load |
|||||
Output wave form | Pure Sinewave | |||||
Output frequency | 50/60Hz (±10%) | |||||
Inverter overload capacity (Utility power,25©) |
100-105%: no alarm
105-125% : load transfers to Bypass mode after 10 minutes
125-150% : load transfers to Bypass mode after 30s
|
|||||
Transfer time | 0ms | |||||
Crest factor | 3:1 | |||||
DISPLAY/ INTERFACE | LCD Display | LCD Display indicates frequency, voltage, load, battery voltage, etc. LED indicates running status | ||||
LED Status Indicator | Utility power; Battery discharge; Inverter On | |||||
External Communication | USB/RS485 and (RS232 and SNMP adapter are optional) | |||||
PARALLEL | 4 Units | |||||
Communication software |
Windows XP/ 2003 and later version; Linux; Unix | |||||
Optional | EX SNMP / dry contact relays / Modbus | |||||
Battery | Batteries voltage | 360VDC | 360VDC | 384VDC | 384VDC | |
Battery Type | Sealed maintenance-free lead –acid battery | |||||
Backup Time (25℃) |
Full load ≥ 5min (Standard) | |||||
Battery quantity | 30 | 30 | 64 | 64 | ||
General | Temperature | 0 ~ 40℃ | ||||
Humidity | <95% (non-condensing) | |||||
Altitude | <1000m | |||||
Efficiency | >90% (Line mode), >92% (Battery mode), >96% (Eco mode) | |||||
FUNCTIONS | Expandable Battery Modules, LCD | |||||
Noise (dB) | <50dB | |||||
Protection | Low battery, overload, over temperature, short circuit, output over voltage, output low voltage | |||||
L*W*H (mm) | 500 x 300 x 650 | 500 x 300 x 650 | 590 x350 700 | 630 x350 x810 | ||
Weight (kg) | 76 | 80 | 98 | 218 | 260 |