Dalton UPS ES33 Series
Dalton ES33 Online Double Conversion UPS
With Isolation Transformer
160kVA – 500kVA
The large capacities of ES33-Frindly Uninterruptible power supply is
a combination of Dalton’s advanced digital signal processor ( DSP) control
technology and a firm pursuit of a green manufacturing philosophy.
With minimum space, fewer components and controlled levels of noise pollution.
The ES33 Series has a significantly reduced environmental impact.
Therefore, it is feasible to design a UPS with reduced carbon footprint whilst
achieving clean, continuous power for heavy medical,industrial and computing loads.
– Output Factor 0.9
– Online double conversion & Input IGBT Rectifier
– 3 phases UPS allow 100% unbalance load
– IGBT inverter and output isolation transformer
– Fully DSP control, high reliability and performance
– Dual input supplies
Specifications
Model | ES33160 | ES33200 | ES33250 | ES33300 | ES33400 | ES33500 |
Power Rating | 160 KVA 144 KW |
200 KVA 180 KW |
250 KVA 225 KW |
300 KVA 270 KW |
400 KVA 360 KW |
500 KVA 450 KW |
INPUT | ||||||
Rated voltage | 380 V / 400 V / 415 VAC | |||||
Voltage range | 346 V ~ 456 V (full load) 304 V ~ 346 V (voltage rating 10%) |
|||||
Rated frequency | 50 / 60 Hz | |||||
Frequency range | 50 / 60 Hz ± 5 Hz | |||||
Power factor | ≥ 0.99 | |||||
Total harmonic distortion (THDI) | ≤ 3% | |||||
Input current-limiting | 1.1 times of rated current (0.1 ~ 1.1 settable ) | |||||
Rectifier delay start | 10 s (1 ~ 300 settable) | |||||
Bypass voltage range | ± 20% (settable) | |||||
OUTPUT | ||||||
Rated voltage | 380 V / 400 V / 415 VAC | |||||
Voltage regulation | ± 1% | |||||
Frequency | Synchronized with utility in mains mode; 50 / 60 Hz ± 0.1% in battery mode | |||||
Waveform | Pure sinewave | |||||
Crest factor | 3:1 | |||||
Total harmonic distortion (THDV) | ≤ 2% (resistive load); ≤ 5% (non-linear load) | |||||
Transfer time | 0 ms | |||||
Inverter overload capability | Load ≤ 105%,long time work: 105% < load ≤ 110%,transfer to bypass in 60 min 110% < load ≤ 125%, transfer to bypass in 10 min 125% < load ≤ 150%, transfer to bypass in 1 min 150% < load ≤ 200%, transfer to bypass in 200 ms 200% < load, inverter off (UPS shutdown) in 100 ms and transfer to bypass output |
|||||
Slight adjustment of inverter out- put voltage |
± 5 V | |||||
BATTERIES | ||||||
DC voltage | 600 VDC (support 576 VDC / 588 VDC/ 612 VDC / 624 VDC) | |||||
Number of battery | 50 pcs ( support 48 / 49 / 51 / 52 pcs) | |||||
Charging current | Charging rate (settable) × battery capacity (settable) × number of battery group (settable) | |||||
Battery state display | Battery remaining capacity and backup time | |||||
Battery self-test | Settable periodic self-test; manually configurable test time and voltage | |||||
SYSTEM | ||||||
Efficiency | Line mode ≥ 94%, ECO mode ≥ 98% | |||||
Max. parallel numbers | 6 | |||||
Protections | Short-circuit, overload, over temperature, over voltage, under voltage, battery low voltage and fan failure ( EPO ) |
|||||
Communications | RS232 / RS485 / dry contacts (standard), SNMP (optional) | |||||
IP rating | IP 20 | |||||
Display | 6 inches LCD touch screen | |||||
OTHERS | ||||||
Operating temperature | 0 ~ 40℃ | |||||
Storage temperature | - 25℃ ~ 55℃ (without battery) | |||||
Humidity | 0 ~ 95% (non-condensing) | |||||
Noise level at 1 m | < 65 dB | < 70 dB | ||||
Dimensions (W×L×H) (mm) | 780 × 820 × 1650 | 1200 × 830 × 1900 | 2380 × 1560 × 1950 | |||
Net / Gross weight (kg) | 750 / 780 | 1000 / 1100 | 1160 / 1300 | 1222 / 1310 | 1990 / 2120 | 2210 / 2300 |