DALTON UPS B33 SERIES
B33 Smart Online Double Conversion UPS
Three Phase Input & Output
10KVA – 120KVA
Dalton B33 is a state-of-the-art uninterruptible power supply, achieving
the highest possible level of on-line double-conversion performance (VFI-SS-111)
as defined within IEC EN 62040-3.
The sizes available include: 10-15-20-30-40-60-80-100-120 kVA all with a three-phase input and output.
B33 is one of the most efficient UPS available with a minimal impact on its environment and power sources.
– Transformer less UPS Technology
– Output power factor 1.0
– Optional SNMP communication port
– Maintenance bypass switch
– Output short circuit & overload protections
– Optional dual input supplies
Specifications
Model | B3310 10K |
B3315 15K |
B3320 20K |
B3330 30K |
B3340 40K |
B3360 60K |
B3380 80K |
B33100 100K |
B33120 120K |
|
Rating Power | 10KVA 10KW |
15KVA 15KW |
20KVA 20KW |
30KVA 30KW |
40KVA 40KW |
60KVA 60KW |
80KVA 80KW |
100KVA 100KW |
120KVA 120KW |
|
Input | Input system | 3 Phases + N & earth ground | ||||||||
Voltage range | 380/400/415}25% | |||||||||
Power factor | ≥0.99 | |||||||||
Frequency | 50/60}10%5% optional | |||||||||
Output | Output system | 3 Phases + N & earth ground | ||||||||
Rated voltage | L-N:220/230/240}1%, L-L:380/400/415}1%, | |||||||||
Power factor | 1 | |||||||||
Voltage precision | ±2% | |||||||||
Voltage distortion | THD≤2% (linear load) | |||||||||
Output waveform | Pure Sinewave | |||||||||
Output frequency | 50/60}0.2 (battery mode) | |||||||||
Inverter overload capacity (Utility power, 25Co) |
125% load for 10mins, 150% load for 1 min | |||||||||
Transfer time | 0ms | |||||||||
Crest factor | 3:1 | |||||||||
DISPLAY/ INTERFACE | LCD Display | LCD Display indicates frequency, voltage, load, battery voltage, etc. LED indicates running status | ||||||||
LED Status Indicator | Utility power; Battery discharge; Inverter On | |||||||||
External Communication | MODBUS/RS485 and dry contact (RS232 and SNMP adapter are optional) | |||||||||
Display | Touch screen + LED | |||||||||
Communication software | Windows XP/ 2003 and later version; Linux; Unix | |||||||||
Optional | SNMP Card/ Dry Contact AS400 Card/ CMC Card/ RS485 Card/ EMD Monitoring Device | |||||||||
Battery | Batteries voltage | 348 (360 setting) | 384(348/360/372 setting) | |||||||
Battery Type | Sealed maintenance-free lead –acid battery / Gel Battery / NiCd | |||||||||
Backup Time (25Co) | Full load ≥ 5min (Standard) | |||||||||
Battery quantity | 32 | 32 (29,30,31) | ||||||||
General | Temperature | 0 ~ 40℃ | ||||||||
Humidity | 0 ~ 95%, No condensation | |||||||||
Altitude | <1000m | |||||||||
Efficiency | Line: ≥ 97% | |||||||||
Alarm | Overload, abnormal AC input, low battery, UPS failure | |||||||||
Noise (dB) | <40 | < 50 - 60 | ||||||||
Protection | Low battery, overload, over temperature, short circuit, output over voltage, output low voltage | |||||||||
L*W*H (mm) | 630×253×830 | 810x300x1010 | 815×370×1015 | 950×585×1400 | ||||||
Weight (kg) | 29 | 43 | 50 | 62 | 71 | 111 | 117 | 199 - 241 |