DALTON UPS U33 SERIES
U31 Plus Smart Online Double Conversion UPS
Three Phase 3:1 Dalton U31 Plus
10KVA – 40KVA
The On-Line- Transformer Based Series is an uninterruptible power supply incorporating
double-converter technology. Medical provides perfect protection specifically for strict load.
The double-converter principle eliminates all mains power disturbances.
In the event of power failure, the maintenance-free batteries power the inverter.
Designed with the Galvanic Isolation Transformer for output
UPS offers the greatest degree of availability in power protection and provides
continuous high-quality AC power to connect strict load,.
– Transformer Based UPS Technology
– Output Short Circuit and Overload Protection
– Cold Start Function
– Optional SNMP Communication Port
– Maintenance Bypass Switch
Specifications
384VDC
Model |
U31 Plus
10K
|
U31 Plus
15K
|
U31 Plus 20K |
U31 Plus 20K |
U31 Plus
30K
|
U31 Plus
40K
|
|||
Power Rating | 10KVA/8KW-15KVA/12KW | 20KVA/16KW | 30KVA/24KW | 40KVA/32KW | |||||
Input | Input system | 3 Phases + N & earth ground | |||||||
Voltage range | 285~485VAC(full load) | ||||||||
Power factor | ≥0.99 | ||||||||
Frequency | 40~60Hz (50Hz ) /50~70Hz (60Hz) | ||||||||
Output | Output system | 3 Phases + N & earth ground | |||||||
Rated voltage | 220/230/240VAC / | ||||||||
Power factor1 | 0.8 | ||||||||
Voltage precision | ±2% | ||||||||
Voltage distortion | Linear≤2% on R 100% loading (line) | ||||||||
Output waveform | Pure Sine Wave | ||||||||
Output frequency | Normal mode |
(1)synchronized 46~54Hz (2)50Hz(line 40~46 or 54~60Hz) |
|||||||
Battery mode |
50Hz,60Hz | ||||||||
Inverter overload capacity (Utility power, 25oC) |
105% - 125% transfers to bypass mode after 1 minutes; 125% ± 5%< load ≤ 150% ± 5% transfers to bypass mode after 30second |
||||||||
Transfer time | 0ms | ||||||||
Crest factor | 3:1 | ||||||||
DISPLAY/ INTER- FACE | LCD Display | AC/ DC voltages; KVA/ KW; Frequency; Temperature; Battery & load level | |||||||
LED Status Indicator | Utility power; Battery discharge; Inverter On | ||||||||
External Communication | RS232 / RJ11 / USB Card / Optional Intelligent Slot | ||||||||
Control | 3 control push button for POWER ON / POWER OFF / FUNCTION KEY | ||||||||
Communication software | Windows XP/ 2003 and later version; Linux; Unix | ||||||||
Optional | SNMP Card/ Dry Contact AS400 Card/ CMC Card/ RS485 Card/ EMD Monitoring Device | ||||||||
Battery | Batteries voltage |
+/-192VDC
|
384VDC | 384VDC | 384VDC | ||||
Battery Type | Sealed maintenance-free lead –acid battery / Gel Battery / NiCd | ||||||||
Backup Time (25oC) | Full load ≥ 5min (Standard) | ||||||||
Battery quantity | 32*7Ah | 32*9Ah | 32*18Ah | 32*20Ah | |||||
Charge current | 2/4/6/8A | 4/6/8/10/12A | 4/6/8/10/12A | 4/6/8/10/12A | 2/4/6/8/10/12/14/16A | ||||
General | Temperature | 0℃-40℃ | |||||||
Humidity | <95% | ||||||||
Altitude | <1000m | ||||||||
Efficiency | Line: ≥ 90% | ||||||||
Inputs | ECO/EPO | ||||||||
Noise (dB) | ≤ 65dB | ||||||||
Protection | IP20 | ||||||||
L*W*H (mm) | 556X405X795 | 599x405x807 | 650x405x815 - 650x405x815 - 660x405x820 | ||||||