Online transformer based UPS TS31 Plus

Dalton TS31 Plus Online Double Conversion UPS Three Phase Input Single phase output
With Isolation Transformer
10kVA – 50kVA
The output isolation transformer provides high reliability to adapt
different harsh industrial environments and protects the critical
loads 100% 3-phase unbalance load adapt to different kinds of applications.
Dual power supply redundancy.
Wide input voltage range provides high adaptability to the grid and
extend the battery service life Main PCB board with professional
electromagnetic shielding improve reliable performance of EMC
Dual air ducts design offer good cooling to protect the
components and extend the service life1
– True galvanic isolation transformer design
– Output power factor 0.8
– Small Footprint
– High Efficiency 95%
– All Series Touch Screen Design
– DSP technology guarantees high reliability
Specifications
Model |
TS3110000PLUS
10K
|
TS3115000PLUS
15K
|
TS3120000PLUS
20K
|
TS3130000PLUS
30K
|
TS3140000PLUS
40K
|
TS3150000PLUS
50K
|
||||
Rating Power |
10KVA
8KW
|
15KVA
12KW
|
20KVA
16KW
|
30KVA
24KW
|
40KVA
32KW
|
50KVA
40KW
|
||||
Input | Input system | 3 Phases + N & earth ground | ||||||||
Voltage range | 380/400/415}25% | |||||||||
Power factor | ≥0.99 | |||||||||
Frequency | 50/60}10%5% optional | |||||||||
Output | Output system | Single Phases + N & earth ground | ||||||||
Rated voltage | L-N:220/230/240 | |||||||||
Power factor | 0.8 | |||||||||
Voltage precision | ±1% | |||||||||
Voltage distortion | THD≤2% (linear load) | |||||||||
Output waveform | Pure Sinewave | |||||||||
Output frequency | 50/60}0.2 (battery mode) | |||||||||
Inverter overload capacity
(Utility power, 25Co)
|
125% load for 10mins, 150% load for 1 min | |||||||||
Transfer time | 0ms | |||||||||
Crest factor | 3:1 | |||||||||
DISPLAY/ INTERFACE | LCD Display | LCD Display indicates frequency, voltage, load, battery voltage, etc. LED indicates running status | ||||||||
LED Status Indicator | Utility power; Battery discharge; Inverter On | |||||||||
External Communication | MODBUS/RS485 and dry contact (RS232 and SNMP adapter are optional) | |||||||||
Display | Touch screen + LED | |||||||||
Communication software | Windows XP/ 2003 and later version; Linux; Unix | |||||||||
Optional | SNMP Card/ Dry Contact AS400 Card/ CMC Card/ RS485 Card/ EMD Monitoring Device | |||||||||
Battery | Batteries voltage | 348 (360 setting) | 384(348/360/372 setting) | |||||||
Battery Type | Sealed maintenance-free lead –acid battery / Gel Battery / NiCd | |||||||||
Backup Time (25Co) | Full load ≥ 5min (Standard) | |||||||||
Battery quantity | 32 | 32 (29,30,31) | ||||||||
General | Temperature | 0 ~ 40℃ | ||||||||
Humidity | 0 ~ 95%, No condensation | |||||||||
Altitude | <1000m | |||||||||
Efficiency | Line: ≥ 95% | |||||||||
Alarm | Overload, abnormal AC input, low battery, UPS failure | |||||||||
Noise (dB) | <55 | < 60 - 65 | ||||||||
Protection | Low battery, overload, over temperature, short circuit, output over voltage, output low voltage | |||||||||
L*W*H (mm) | 656×405×817 | 821x432x1159 | ||||||||
Weight (kg) | 145 | 195 | 280 | 365 | 475 | 580 | 740 - 800 |